Fluke1587 FC 絶縁マルチメーター

  • Fluke 1587 FC Insulation Multimeter
  • Fluke 1587 FC Insulation Multimeter
  • Fluke 1587 FC Insulation Multimeter
  • Fluke 1587 FC Insulation Multimeter
  • Video Player is loading.
    Current Time 0:00
    Duration 0:00
    Loaded: 0%
    Stream Type LIVE
    Remaining Time 0:00
     
    1x
      • Chapters
      • descriptions off, selected
      • subtitles off, selected
      • Video Player is loading.
        Current Time 0:00
        Duration 0:00
        Loaded: 0%
        Stream Type LIVE
        Remaining Time 0:00
         
        1x
          • Chapters
          • descriptions off, selected
          • subtitles off, selected
          1. Fluke 1587 FC Insulation Multimeter
          2. Fluke 1587 FC Insulation Multimeter
          3. Fluke 1587 FC Insulation Multimeter
          4. Fluke 1587 FC Insulation Multimeter
          5. Fluke 1587 FC Tips and Tricks
          6. How to test a motor with the 1587 FC

          主な機能

          続きを読む

          製品概要: Fluke1587 FC 絶縁マルチメーター

          高性能 2-in-1 絶縁 DMM

          Fluke 1587 FC 絶縁マルチメーターは、充実した機能を備えた、True-rms デジタル・マルチメーター機能を持つデジタル絶縁テスターです。単一のコンパクトな携帯型のユニットから構成され、トラブルシューティングと予防保守の両面で、さまざまな用途に使用可能な優れた汎用性があります。

          Fluke 1587 FC 絶縁マルチメーターでは、Fluke Connect® 測定アプリを使用することにより、次の 4 つの強力な診断機能を追加できます。

          • TrendIt™ グラフを使用した PI/DAR 時間比試験により、湿度や汚れによる絶縁の問題を効率的に特定
          • Fluke Connect によるメモリー保存機能により、結果を書き留めておく必要がないため、ミスが少なくなり、データを保存して履歴を追跡することも可能
          • アプリによる温度補正により、正確なベースラインと関連履歴比較を確立
          • Fluke Connect® Assets の履歴追跡およびアセット傾向分析により、経年劣化を特定し、現場でリアルタイムに判断を下すことが可能

          製品の特長

          • PI/DAR 時間比試験
          • 30 V を超える電圧が検出された場合ライブ・サーキット検出で絶縁テストを中止し、ユーザー保護を強化
          • 正確なモーター・ドライブ測定のための VFD ローパス・フィルター
          • 容量性電圧の自動放電によるユーザーの保護
          • 絶縁試験 (1587 FC: 0.01 MΩ ~ 2 GΩ)
          • 各種用途に対応する絶縁テスト電圧 (1587 FC: 50 V、100 V、250 V、500 V、1000 V)
          • AC/DC 電圧、DC (ミリボルト)、 AC/DC (ミリアンペア)、抵抗 (Ω)、導通
          • 静電容量、ダイオード・テスト、温度、最小/最大、周波数 (Hz)
          • バッテリーを節約する自動電源オフ
          • CAT III 1000 V、CAT IV 600 V の測定カテゴリー
          • バックライト付き大型ディスプレイ
          • 堅牢なユーティリティ・ハード・ケースにより、作業に必要なすべての機能を常に手元に
          • 付属アクセサリー: リモート・プローブ、テスト・リード、ワニ口クリップ、K 型熱電対
          • オプションで Fluke TPAK 磁石式メーター吊り下げキットを使用できるため、ハンド・フリー操作にも便利
          • 標準保証期間 3 年、購入後 45 日以内に製品登録することにより、5 年間に延長可能

          仕様: Fluke1587 FC 絶縁マルチメーター

          Electrical Specifications
          AC voltage measurement
          Range
          600.0 mVResolution0.1 mV
          Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
          Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)±(2% + 3)
          6.000 VResolution0.001 V
          Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
          Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)±(2% + 3)
          60.00 VResolution0.01 V
          Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
          Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)±(2% + 3)
          600.0 VResolution0.1 V
          Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
          Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)±(2% + 3)¹
          1000 VResolution1 V
          Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(2% + 3)
          Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)±(2% + 3)¹
          ¹ 1 kHz bandwidth
          Low-Pass Filter Voltage 
          Range
          600.0 mVResolution0.1 mV
          Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
          Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)+(2% + 3), -(6% - 3)
          6.000 VResolution0.001 V
          Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
          Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)+(2% + 3), -(6% - 3)
          60.00 VResolution0.01 V
          Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
          Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)+(2% + 3), -(6% - 3)
          600.0 VResolution0.1 V
          Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
          Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)+(2% + 3), -(6% - 3)
          1000 VResolution1 V
          Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(2% + 3)
          Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)+(2% + 3), -(6% - 3)
          DC Voltage Measurement
          RangeResolutionAccuracy ±(% of Rdg + Counts)
          6.000 V dc0.001 V±(0.09% + 2)
          60.00 V dc0.01 V±(0.09% + 2)
          600.0 V dc0.1 V±(0.09% + 2)
          1000 V dc1 V±(0.09% + 2)
          Input impedance 10 MΩ (nominal), <100 pF
          Normal mode rejection ratio >60 dB @ 50 Hz or 60 Hz
          Common mode rejection ratio >120 dB @ dc, 50 Hz or 60 Hz (1 k unbalance)
          Accuracies apply to ± 100% of range
          DC Millivolts Measurement
          RangeResolutionAccuracy ±(% of Rdg + Counts)
          600.0 mVdc0.1 mV±(0.1% + 1)
          DC and AC Current Measurement
          AC 45 Hz to 1000 Hz
          Range400 mA
          Resolution0.1 mA
          Accuracy ±(% of Rdg+Counts)±(1.5% + 2)¹
          Burden voltage (Typical)2 mV/mA
          Range60 mA 
          Resolution0.01 mA 
          Accuracy ±(% of Rdg+Counts)±(1.5% + 2)¹
          Burden voltage (Typical)2 mV/mA
          DC
          Range400 mA
          Resolution0.1 mA
          Accuracy ±(% of Rdg+Counts)±(0.2% + 2)
          Burden voltage (Typical)2 mV/mA
          Range60 mA
          Resolution0.01 mA
          Accuracy ±(% of Rdg+Counts)±(0.2% + 2)
          Burden voltage (Typical)2 mV/mA
          Overload600 mA for 2 minutes maximum
          Fuse protection for mA input0.44 mA, 1000 V, IR 10 kA
          AC conversionInputs are ac-coupled and calibrated to the rms value of sine wave input
          Conversions are true-rms responding and specified from 5% to 100% of range. Input signal crest factor can be up to 3 up to 300 mA, decreasing linearly to crest factor ≤1.5 at 600 mA. For non-sinusoidal waveforms add +(2% reading + 2% FS) typical, for a crest factor up to 3.
          ¹ 1 kHz bandwidth
          Ohms Measurement
          RangeResolutionAccuracy +(% of Rdg+Counts)¹
          600.0 Ω0.1 Ω±(0.9% + 2)
          6.000 kΩ0.001 kΩ±(0.9% + 2)
          60.00 kΩ0.01 kΩ±(0.9% + 2)
          600.0 kΩ0.1 KΩ±(0.9% + 2)
          6.000 MΩ0.001 MΩ±(0.9% + 2)
          50.0 MΩ ²0.01 MΩ±(1.5% + 3)
          Overload protection 1000 V rms or dc
          Open circuit test voltage <8.0 V dc
          Short circuit current <1.1 mA
          ¹ Accuracies apply from 0% to 100% of range
          ² Up to 80% relative humidity
          Diode Test
          Diode test indicationDisplay voltage drop: 0.6 V at1.0 mA nominal test current:
          Accuracy±(2% + 3)
          Continuity Test
          Continuity indicationContinuous audible tone for testresistance below 25 Ω and off above 100 Ω. Maximum Reading; 1000 Ω
          Open circuit voltage<8.0 V
          Short circuit current1.0 mA typical
          Overload protection1000 V rms
          Response time>1 m sec
          Frequency Measurement
          RangeResolutionAccuracy ±(% of Rdg+Counts)
          99.99 Hz 0.01 Hz ±(0.1% + 1)
          999.9 Hz 0.1 Hz ±(0.1% + 1)
          9.999 kHz 0.001 kHz ±(0.1% + 1)
          99.99 kHz 0.01 kHz ±(0.1% + 1)
          Frequency Counter Sensitivity
          600.0 mV ac V ac Sensitivity (RMS Sine Wave)¹  5 Hz to 20 kHz 100.0 mV 
          V ac Sensitivity (RMS Sine Wave)¹  20 kHz to 100 kHz150.0 mV 
          DC Trigger Levels¹ to 20 kHz²NA
          6.0 V V ac Sensitivity (RMS Sine Wave)¹  5 Hz to 20 kHz 1.0 V 
          V ac Sensitivity (RMS Sine Wave)¹  20 kHz to 100 kHz1.5 V 
          DC Trigger Levels¹ to 20 kHz²-400.0 mV and 2.5 V
          60.0 V V ac Sensitivity (RMS Sine Wave)¹  5 Hz to 20 kHz 10.0 V 
          V ac Sensitivity (RMS Sine Wave)¹  20 kHz to 100 kHz36.0 V 
          DC Trigger Levels¹ to 20 kHz²1.2 V and 4.0 V
          600.0 V V ac Sensitivity (RMS Sine Wave)¹  5 Hz to 20 kHz 100.0 V 
          V ac Sensitivity (RMS Sine Wave)¹  20 kHz to 100 kHz-
          DC Trigger Levels¹ to 20 kHz²12.0 V and 40.0 V
          1000.0 V V ac Sensitivity (RMS Sine Wave)¹  5 Hz to 20 kHz 300.0 V 
          V ac Sensitivity (RMS Sine Wave)¹  20 kHz to 100 kHz-
          DC Trigger Levels¹ to 20 kHz²12.0 V and 40.0 V
          ¹ Maximum input for specified accuracy = 10x range (1000 V max). Noise at low frequencies and amplitudes may affect accuracy
          ² Usable to 100 kHz with full scale input
          Capacitance
          Range Resolution Accuracy ±(% of Rdg+Counts)
          1000 nF 1 nF±(1.2% + 2)
          10.00 μF 0.01 μF±(1.2% + 2)
          100.0 μF 0.1 μF±(1.2% ±90 counts)
          9999 μF 1 μF±(1.2% ±90 counts)
          Temperature Measurement
          Range Resolution Accuracy ±(% of Rdg+Counts)¹
          -40 ° C to 537 ° C 0.1 °C ±(1% + 10 counts)
          -40 ° F to 998 ° F 0.1 °F ±(1% + 18 counts)
          ¹ Accuracies apply following 90 minutes settling time after a change in the ambient temperature of the instrument
          Insulation Specifications
          Measurement range0.01 MΩ to 2 GΩ
          Test voltages50, 100, 250, 500, 1000 V
          Test voltage accuracy+20%, -0%
          Short-circuit test current1 mA nominal
          Auto dischargeDischarge time <0.5 second for C = 1 μF or less
          Live circuit detectionInhibit test if terminal voltage > 30 V prior to initialization of test
          Maximum capacitive loadOperable with up to 1 μF load
          Output Voltage
          50 V (0% to +20%)Display range0.01 to 6.00 MΩ
          Resolution0.01 MΩ
          Test current1 mA @ 50 kΩ
          Resistance accuracy ±(% of Rdg + Counts)±(3% + 5 counts)
          Display range6.0 to 50.0 MΩ
          Resolution0.1 MΩ
          Test current1 mA @ 50 kΩ
          Resistance accuracy ±(% of Rdg + Counts)±(3% + 5 counts)
          100 V (0% to +20%)Display range0.01 to 6.00 MΩ
          Resolution0.01 MΩ
          Test current1 mA @ 100 kΩ
          Resistance accuracy ±(% of Rdg + Counts)±(3% + 5 counts)
          Display range6.0 to 60.0 MΩ
          Resolution0.1 MΩ
          Test current1 mA @ 100 kΩ
          Resistance accuracy ±(% of Rdg + Counts)±(3% + 5 counts)
          Display range60 to 100 MΩ 
          Resolution1 MΩ
          Test current1 mA @ 100 kΩ
          Resistance accuracy ±(% of Rdg + Counts)±(3% + 5 counts)
          250 V (0% to +20%)Display range0.1 to 60.0 MΩ 
          Resolution0.1 MΩ
          Test current1 mA @ 250 kΩ 
          Resistance accuracy ±(% of Rdg + Counts)±(1.5% + 5 counts)
          Display range60 to 250 MΩ 
          Resolution1 MΩ
          Test current1 mA @ 250 kΩ 
          Resistance accuracy ±(% of Rdg + Counts)±(1.5% + 5 counts)
          500 V (0% to +20%)Display range0.1 to 60.0 MΩ
          Resolution0.1 MΩ
          Test current1 mA @ 500 kΩ 
          Resistance accuracy ±(% of Rdg + Counts)±(1.5% + 5 counts)
          Display range60 to 500 MΩ
          Resolution1 MΩ
          Test current1 mA @ 500 kΩ 
          Resistance accuracy ±(% of Rdg + Counts)±(1.5% + 5 counts)
          1000 V (0% to +20%)Display range0.1 to 60.0 MΩ 
          Resolution0.1 MΩ
          Test current1 mA @ 1 MΩ
          Resistance accuracy ±(% of Rdg + Counts)±(1.5% + 5 counts)
          Display range60 to 600 MΩ 
          Resolution1 MΩ
          Test current1 mA @ 1 MΩ
          Resistance accuracy ±(% of Rdg + Counts)±(1.5% + 5 counts)
          Display range0.6 to 2.0 GΩ 
          Resolution100 MΩ 
          Test current1 mA @ 1 MΩ
          Resistance accuracy ±(% of Rdg + Counts)±(10% + 3 counts)
          General Specifications
          Maximum voltage applied to any terminal and common1000 V
          Storage temperature-40 °C to 60 °C (-40 °F to 140 °F)
          Operating temperature-20 °C to 55 °C (-4 °F to 131 °F)
          Temperature coefficient0.05 x (specified accuracy) per °C for temperatures <18 °C or >28 °C (<64 °F or >82 °F)
          Relative humidityNoncondensing
          0% to 95% @ 10 °C to 30 °C (50 °F to 86 °F)
          0% to 75% @ 30 °C to 40 °C (86 °F to 104 °F)
          0% to 40% @ 40 °C to 55 °C (104 °F to 131 °F)
          VibrationRandom, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument
          Radio frequency communication2.4 GHz ISM Band
          Radio frequency certificationFCC: T68-FBLE, IC: 6627A-FBLE
          Electromagnetic Compatibility 
          InternationalIEC 61326-1:Portable Electromagnetic Environment; IEC 61326-2-2 CISPR 11: Group 1, Class A
          Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself.
          Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes.  There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances.
          Emissions that exceed the levels required by CISPR 11 can occur when the equipment is connected to a test object. The equipment may not meet the immunity requirements of this standard when test leads and/or test probes are connected.
          Korea (KCC)Class A Equipment (Industrial Broadcasting & Communication Equipment)
          Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes.
          USA (FCC)47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103.
          Enclosure protectionIEC 60529: IP40 (non-operating)
          Safety
          IEC 61010-1Pollution Degree 2
          IEC 61010-2-033CAT IV 600 V / CAT III 1000 V
          Batteries Four AA batteries (IEC LR6)
          Battery lifeMeter use 1000 hours; Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
          Size (H x W x L)5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in)
          Weight550 g (1.2 lb)
          AltitudeOperating2000 m
          Storage12,000 m
          Over-range capability110% of range except for capacitance which is 100%
          Frequency overload protection<107 V Hz
          Fuse protection for mA input0.44A, 1000 V, IR 10 kA

          モデル: Fluke1587 FC 絶縁マルチメーター

          FLK-1587-FC

          Fluke1587 FC 絶縁マルチメーター


          購入する

          の内容:

          • リモート・プローブ
          • テスト・リード
          • アリゲータークリップ
          • Kタイプ熱電対
          • ソフトケース
          • ユーザー・ドキュメント