Product selection guide: IR windows

Use our product selection guide to find the IR window that fits your needs best.
 
RemoveRemove
 
 
Fluke 075 CLKT IR Window for Outdoor and Indoor Applications
Fluke CV400 ClirVu® 95 mm (4 in) Infrared Window
 
Fluke CV301 ClirVu® 75 mm (3 in) Infrared WindowFluke CV400 ClirVu® 95 mm (4 in) Infrared Window
 
Size76 mm (3 in)95 mm (4 in) 
Voltage rangeAnyAny 
NEMA environment typeType 4/12 (indoor/outdoor)Type 4/12 (indoor/outdoor) 
AutoGround™   
ClirVu® Optic   
Operating temperature-40 °C to +232 °C (-40 °F to +450 °F) and +260 °C (+500 °F) intermittent-40 °C to +232 °C (-40 °F to +450 °F) and +260 °C (+500 °F) intermittent 
Arc-tested (IEEE C27.20.7)66 kA for 30 cycles @ 60 Hz at KEMA63 kA for 30 cycles @ 60 Hz at KEMA 
UL 50/NEMA environmental ratingNEMA type 4/15NEMA type 4/12 
UL 1558   
CSA C22.2 No.   
CSA type ratingType 7Type 4 
IP ratingIP 67 at TUVIP 67 at TUV 
Lloyd's RegisterUp to 11 kV marine switchgear, indoor or outdoor (offshore only)Up to 11 kV marine switchgear, indoor or outdoor (offshore only) 
Vibration ratingIEC60068-2-6 at TUVIEC60068-2-6 at TUV 
Humidity rateIEC60068-2-3 at TUVIEC60068-2-3 at TUV 
UL 50 V component recognition  
Actual mounting hole diameter required89.89 mm (3.539 in)115.42 mm (4.544 in) 
Greenlee punch kit - punch/die739BB = 1431AV / 1432AV742BB = 2984AV / 2983AV 
Door latchSecurity keyHand turn 
Install time8 minutes or less5 minutes or less 
Optic insert diameter76 mm (2.96 in)95 mm (3.74 in) 
WarrantyLifetime replacement against manufacturing defectsLifetime replacement against manufacturing defects