Multimetro a pinza TRMS CAT III 1500 V 393 FC con iFlex

  • 393 FC CAT III 1500 V True-rms Clamp Meter
  • The Fluke 393 clamp meter has a very thin jaw for cramped combiner boxes, but still clamps around a 34 mm cable.
  • Fluke 393 FC clamp calculates and dsiplay dc power (kVA) enerated by a solar panel
  • Measurements sent to a smartphone and the cloud via Fluke Connect software.
  • Video Player is loading.
    Current Time 0:00
    Duration 0:00
    Loaded: 0%
    Stream Type LIVE
    Remaining Time 0:00
     
    1x
      • Chapters
      • descriptions off, selected
      • en (Main), selected
    1. 393 FC CAT III 1500 V True-rms Clamp Meter
    2. The Fluke 393 clamp meter has a very thin jaw for cramped combiner boxes, but still clamps around a 34 mm cable.
    3. Fluke 393 FC clamp calculates and dsiplay dc power (kVA) enerated by a solar panel
    4. Measurements sent to a smartphone and the cloud via Fluke Connect software.
    5. Fluke 393 FC CAT III 1500 V True-rms Clamp Meter

    Caratteristiche principali

    • Misurazioni in sicurezza con un multimetro a pinza da 1500 V nominali CAT III
    • Ganascia sottile per l'accesso ai cavi in scatole di giunzione stipate
    • Robusto con grado di protezione IP54 per l'uso all'aperto 
    • Possibilità di lavorare in modo efficiente con la misurazione della potenza DC, la polarità audio e la continuità visiva

    Descrizione generale del prodotto: Multimetro a pinza TRMS CAT III 1500 V 393 FC con iFlex

    Il multimetro a pinza elettrosolare TRMS Fluke 393 FC CAT III 1500 V con iFlex è progettato per i tecnici addetti all’installazione di impianti fotovoltaici e i professionisti della manutenzione che lavorano in ambienti DC ad alta tensione: Array fotovoltaici, energia eolica, ferrovie elettriche, centri dati, gruppi batterie per gruppi di continuità. Il multimetro a pinza misura fino a 1500 V DC e 1000 V AC con i puntali e fino a 999,9 A DC o AC tramite la ganascia della pinza. La sonda di corrente flessibile iFlex in dotazione estende le misurazioni di corrente AC fino a 2500 A. Il 393 è dotato di una ganascia sottile che permette di accedere ai cavi in combiner box stipate. Inoltre, i puntali sono progettati in modo da agevolare il lavoro e sono anch'essi classificati CAT III 1500 V DC.


    Altre funzioni principali:
    • Grado di protezione IP54, perfetto per lavorare all'aperto su array solari e impianti di produzione di energia eolici 
    • Misurazione della potenza DC, con visualizzazione delle letture in kVA
    • L'indicatore di polarità audio aiuta a evitare errori di cablaggio
    • La continuità visiva fornisce una luce verde brillante sul display, ideale quando si lavora in ambienti bui e rumorosi
    • Registrazione e creazione di report dei risultati dei test tramite il software Fluke Connect
    • Durante la misurazione della corrente AC, la sonda di corrente flessibile iFlex in dotazione offre un accesso senza eguali al cavo in spazi ristretti.  La sonda di corrente iFlex può essere ruotata per inserirla in spazi estremamente ridotti e fornire misurazioni di corrente accurate.
     

    In dotazione:

    • Multimetro a pinza TRMS 1500 V CAT III Fluke 393 FC
    • Puntali, di categoria CAT III 1500 V, connettori maschio ad angolo retto, con cappucci di sicurezza
    • Sonda di corrente flessibile iFlex da 18 pollici
    • Cinghia con aggancio magnetico TPAK
    • Custodia da trasporto Premium
    • 3 anni di garanzia

    Dati tecnici: Multimetro a pinza TRMS CAT III 1500 V 393 FC con iFlex

    Specifiche:   
    Generali   
    Tensione massima tra un qualsiasi terminale e la terra  
    AC1000 V  
    DC1500 V  
    Batterie2 AA IEC LR6 alcaline  
    DisplayDoppio display con retroilluminazione  
    Spegnimento automatico20 minuti  
    Specifiche elettriche   
    Precisione   
    La precisione è specificata per un anno dopo la calibrazione, a temperature di esercizio comprese tra 18 °C e 28 °C e umidità relativa compresa tra 0% e 75%. Le specifiche di precisione sono riportate come segue: ±([% della lettura] + [numero di cifre meno significative]).
    Coefficienti di temperaturaAggiungere 0,1 x la precisione specificata per ogni grado centigrado > 28 °C o < 18 °C
    Corrente AC: Ganascia   
    Range999,9 A  
    Risoluzione0,1 A  
    Precisione2% ± 5 punti (da 10 Hz a 100 Hz) 
     2,5% ± 5 punti (da 100 Hz a 500 Hz) 
    Fattore di cresta (50/60 Hz)2,5 a 600,0 A  
     3,0 a 500,0 A  
     1,42 a 999,9 A  
     Aggiungere 2% per C.F. >2  
    Corrente AC: Sonda di corrente flessibile   
    Range999,9 A  
     2500 A  
    Risoluzione0,1 A (≤999,9 A)  
     1 A (≤2500 A)  
    Precisione3% RD + 5 punti (da 10 Hz a 500 Hz) 
    Fattore di cresta (50/60Hz)2,5 a 1400 A  
     3,0 a 1100 A  
     1,42 a 2500 A  
     Aggiungere 2% per C.F. >2  
    Sensibilità di posizione   
    Simbolo NEC
    Distanza dal valore ottimalei2500-10 Flexi2500-18 FlexErrore
    A0,5” (12,7 mm)1,4” (35,6 mm)±0,5%
    B0,8” (20,3 mm)2,0” (50,8 mm)±1,0%
    C1,4” (35,6 mm)2,5” (63,5 mm)±2,0%
    L'incertezza di misura presuppone una posizione ottimale per il conduttore primario centralizzato, l'assenza di campi elettrici o magnetici esterni e una temperatura che rientra nella gamma di esercizio.
        
    Corrente DC   
    Range999,9 A  
    Risoluzione0,1 A  
    Precisione2% RD + 5 punti[1]  
     [1]Quando si utilizza la funzione ZERO (B) per compensare gli offset.
    Tensione AC   
    Range600,0 V  
     1000 V  
    Risoluzione0,1 V (≤600,0 V)  
     1 V (≤1000 V)  
    Precisione1% RD + 5 punti (da 20 Hz a 500 Hz) 
    Tensione DC   
    Range600,0 V  
     1500 V  
    Risoluzione0,1 V (≤600,0 V)  
     1 V (≤1500 V)  
    Precisione1% RD + 5 punti  
    mV DC   
    Range500,0 mV  
    Risoluzione0,1 mV  
    Precisione1% RD + 5 punti  
    Frequenza corrente: Ganascia   
    RangeDa 5,0 Hz a 500,0 Hz  
    Risoluzione0,1 Hz  
    Precisione0,5% RD + 5 punti  
    Livello di triggerDa 5 Hz a 10 Hz, ≥10 A  
     Da 10 Hz a 100 Hz, ≥5 A  
     Da 100 Hz a 500 Hz, ≥10 A  
    Frequenza corrente: Sonda di corrente flessibile   
    RangeDa 5,0 Hz a 500,0 Hz  
    Risoluzione0,1 Hz  
    Precisione0,5% RD + 5 punti  
    Livello di triggerDa 5 Hz a 20 Hz, ≥25 A  
     Da 20 Hz a 100 Hz, ≥20 A  
     Da 100 Hz a 500 Hz, ≥25 A  
    Frequenza tensione   
    RangeDa 5,0 Hz a 500,0 Hz  
    Risoluzione0,1 Hz  
    Precisione0,5% RD + 5 punti  
    Livello di triggerDa 5 Hz a 20 Hz, ≥5 V  
     Da 20 Hz a 100 Hz, ≥5 V  
     Da 100 Hz a 500 Hz, ≥10 V  
    Potenza DC   
    Range600,0 kVA (range 600,0 V DC)  
     1500 kVA (range 1500 V DC)  
    Risoluzione0,1 kVA  
     1 kVA  
    Precisione2% RD + 2,0 kVA  
     2% RD + 20 kVA  
    Resistenza   
    Range600,0 Ω  
     6000 Ω  
     60,00 kΩ  
    Risoluzione0,1 Ω (≤ 600,0 Ω)  
     1 Ω (≤ 6000 Ω)  
     0,01 kΩ (≤60,00 kΩ)  
    Precisione1% RD + 5 punti  
    Capacità   
    Range100,0 μF  
     1000 μF  
    Risoluzione0,1 μF (≤100,0 μF)  
     1 μF (≤1000 μF)  
    Precisione1% RD + 5 punti  
    Livello di trigger corrente transitoria di inserzione5 A  
    Specifiche meccaniche   
    Dimensioni (L x P x A)281 mm x 84 mm x 49 mm  
    Peso (con batterie)520 g  
    Apertura della ganascia34 mm  
    Diametro della sonda di corrente flessibile7,5 mm  
    Lunghezza del cavo della sonda di corrente flessibile   
    (dalla testa al connettore del circuito elettronico)1,8 m  
    Specifiche ambientali   
    Temperatura di esercizioDa -10 °C a +50 °C  
    Temperatura di stoccaggioDa -40 °C a 60 °C  
    Umidità di esercizioSenza condensa (<10°C)  
     ≤90% di umidità relativa (da 10 °C a 30 °C)  
     ≤75 % di umidità relativa (da 30 °C a 40 °C)  
     ≤45 % di umidità relativa (da 40 °C a 50 °C)  
    Altitudine di esercizio2000 m  
    Altitudine di stoccaggio12.000 m  
    Classe di protezione (IP)IEC 60529: IP54 non in esercizio  
    Compatibilità elettromagnetica (EMC)   
    InternazionaleIEC 61326-1: Ambiente elettromagnetico apparecchiatura portatile; IEC 61326-2-2 CISPR 11: Gruppo 1, Classe A
     Gruppo 1: La batteria genera intenzionalmente e/o utilizza energia a radiofrequenza accoppiata conduttivamente, necessaria per il funzionamento interno dello strumento stesso.
    Classe A: la batteria è idonea per l'uso in tutti gli ambienti diversi da quelli domestici e quelli collegati direttamente a una rete di alimentazione a bassa tensione tipica degli edifici residenziali. In altri ambienti, a causa di disturbi condotti e irradiati, potrebbero esservi potenziali difficoltà a garantire la compatibilità elettromagnetica.
    Attenzione: Questa apparecchiatura non è destinata all'uso in ambienti residenziali e, in tali ambienti, può non fornire un'adeguata protezione alla ricezione radio.
    Corea (KCC)Apparecchiatura di classe A (apparecchiature di trasmissione e comunicazioni industriali)
     Classe A: l'apparecchiatura soddisfa i requisiti per apparecchiature a onde elettromagnetiche industriali e il venditore o l'utente devono tenerne conto. Questa apparecchiatura è destinata all'uso in ambienti aziendali e non deve essere usata in abitazioni private.
    USA (FCC)47 CFR 15 subpart B. Questo prodotto è considerato dispositivo esente ai sensi della clausola 15.103.
    Sicurezza   
    GeneraleIEC 61010-1: Grado di inquinamento 2 
    MisurazioneIEC 61010-2-032: CAT III 1500 V / CAT IV 600 V 
     IEC 61010-2-033: CAT III 1500 V / CAT IV 600 V 
    Specifiche radio wireless   
    Certificazione per le radiofrequenzeFCC ID: T68-FBLE, IC: 6627A-FBLE 
    Gamma di frequenza radio wirelessDa 2400 MHz a 2483,5 MHz  
    Potenza di uscita<100 mW  
    DICHIARAZIONE DI CONFORMITÀ UE SEMPLIFICATA  
    Con la presente, Fluke dichiara che le apparecchiature radio contenute in questo prodotto sono conformi alla Direttiva 2014/53/UE.
    Il testo completo della dichiarazione UE è disponibile al seguente indirizzo Internet:  
    www.fluke.com/en-us/declaration-of-conformity   

    Modelli: Multimetro a pinza TRMS CAT III 1500 V 393 FC con iFlex

    393 FC
    Multimetro a pinza TRMS CAT III 1500 V 393 FC con iFlex

    Acquista

    In dotazione:

    • Multimetro a pinza TRMS 1500 V CAT III Fluke 393 FC con iFlex
    • Puntali, di categoria CAT III 1500 V, connettori maschio ad angolo retto, con cappucci di sicurezza
    • Sonda di corrente flessibile iFlex da 18 pollici
    • Cinghia con aggancio magnetico TPAK
    • Custodia da trasporto Premium
    • 3 anni di garanzia

    Fluke Connect non è disponibile in tutti i paesi.

    *Non tutti i modelli sono disponibili in tutti i Paesi. Verificare con il proprio rappresentante locale Fluke.

    ©2025  Fluke Corporation. Tutti i marchi sono di proprietà dei rispettivi titolari. Smartphone, servizio wireless e piano dati non inclusi nel prezzo di acquisto. I primi 5 GB di memoria sono gratuiti. Compatibile con iPhone 4s e superiore, con iOS 8 o versioni successive, iPad (in formato iPhone sull'iPad), Samsung Galaxy S4 con Android 4.3.x o versioni successive e Samsung Galaxy S, Nexus 5, HTC One e One M8 con Android™ 4.4.x o versioni successive. Apple e il logo Apple sono marchi registrati di Apple Inc., registrati negli Stati Uniti e in altri paesi. App Store è un marchio di servizio di Apple Inc. Google Play è un marchio di Google Inc.