Transients and voltage unbalance

The electrical power issues that most frequently affect industrial plants include voltage sags and swells, harmonics, transients, and voltage and current unbalance.

Row of motors for HVAC system

In a balanced three-phase system, the phase voltages should be equal or very close to equal. Unbalance or imbalance is a measurement of the inequality of the phase voltages. Voltage imbalance is the measure of voltage differences between the phases of a three-phase system. It degrades the performance and shortens the life of three-phase motors.

The impact of the transients on motors can be severe. Motor winding insulation can break down, which can then lead to costly early motor failure and unplanned downtime.

Testing for transient voltage in motors

Transient voltages—temporary unwanted spikes or blips of voltage in an electrical circuit—can come from any number of sources either inside or outside of an industrial plant.

Adjacent loads turning on or off, power factor correction capacitor banks or even distant weather can generate transient voltages on distribution systems. These transients, which vary in amplitude and frequency, can erode or cause insulation breakdown in motor windings

Finding the source of these transients can be difficult because of the frequency of the occurrences and the fact that they symptoms can present themselves in different ways. For example, a transient may appear on control cables that do not necessarily cause equipment damage directly but may disrupt operations.

Fluke 438-II Power Quality and Motor Analyzer

A good way to identify and measure transients is to use a three-phase power quality analyzer with a transient function. The transient function on the meter is set to great than 50V above the normal voltage. The meter’s display will then show the potentially problematic voltage above 50V – the transients.

If no transients are found in an initial measurement, it is a good practice to measure and log the power quality over time with an advanced industrial power quality logger.

What causes unbalanced voltage?

An unbalanced three-phase system can cause three-phase motors and other three-phase loads to experience poor performance or premature failure because of the following:

  • Mechanical stresses in motors due to lower than normal torque output
  • Higher than normal current in motors and three-phase rectifiers
  • Unbalance current will flow in neutral conductors in three-phase wye systems

Voltage unbalance at the motor terminals causes high current unbalance, which can be 6 to 10 times as large as the voltage unbalance. Unbalanced currents lead to torque pulsation, increased vibration and mechanical stress, increased losses, and motor overheating. Voltage and current unbalances could also indicate maintenance issues such as loose connections and worn contacts.

Unbalance can occur at any point throughout the distribution system. Loads should be equally divided across each phase of a panelboard. Should one phase become too heavily loaded in comparison to others, voltage will be lower on that phase. Transformers and three-phase motors fed from that panel may run hotter, be unusually noisy, vibrate excessively, and even suffer premature failure.

How to calculate voltage unbalance

The calculation for determining voltage unbalance is straight forward. The result is the percentage unbalance and can be used to determine next steps in troubleshooting motor issues. There are three steps in the calculation:

  1. Determine the voltage or current average
  2. Calculate the largest voltage or current deviation
  3. Divide the maximum deviation by the average voltage or current and multiply by 100 % unbalance = (Max deviation from average V or I/average V or I) x 100

A manual unbalance calculation is a point-in-time determination of voltage or current unbalance. A motor drive analyzer like the Fluke 438-II will show voltage or current unbalance in real time, including any variations in unbalance.

Related resources

You might also be interested in