Product overview: Fluke 975 AirMeter™

One Tool. Get More Done.

The Fluke 975 AirMeter test tool raises indoor air monitoring to the next level by combining five powerful tools in one, rugged and easy-to-use handheld device. Use the Fluke 975 to optimize HVAC ventilation settings for ASHRAE 62 recommendations, actively monitor conditions that promote a productive environment, and quickly and accurately address occupant comfort complaints the first time.

The Fluke 975 measures:

  • Temperature
  • Velocity
  • Humidity
  • CO2
  • CO

Use the Fluke 975 AirMeter test tool to:

  • Respond to comfort-related calls from occupants.
  • Verify the operation of building HVAC control systems.
  • Determine whether adequate ventilation exists.
  • Monitor air flow and velocity.
  • Test for dangerous carbon monoxide leaks.
  • Perform duct traversals.
  • Optimize HVAC systems to manage energy costs

Specifications: Fluke 975 AirMeter™

Measured Specifications
TemperatureRange-20°C to 50°C (-5°F to 122°F)
Display resolution0.1°C (0.1°F)
Accuracy±0.9°C / ±1.62°F from 40°C to 60°C
±0.5°C / ±1.00°F from 5°C to 40°C
±1.1°C / ±1.98°F from -20°C to 5°C
Relative humidityRange10% to 90% RH, non-condensing
Display resolution1%
Accuracy±2% RH (10% RH to 90% RH)
Air velocityRange50.0 fpm to 3000 fpm
0.25 m/sec to 15 m/sec
Display resolution1 fpm (0.005 m/sec)
Accuracy±4% or 4 fpm1
±4% or 0.02 m/sec1 whichever is greater
1. Accuracy specification only valid for velocity readings above 50 fpm.
C0Range0 to 500 ppm
Display resolution1 ppm
Accuracy±5% or ±3 ppm, whichever is greater, @ 20°C and
50% RH
C02Range0 to 5000 ppm
Display resolution
1 ppm
AccuracyWarm up time 1 min (5 minutes for full specification) 2.75% + 75 ppm
Calculated Specifications
Dew point temperatureRange-44°C to 50°C, (-47°F to 122°F)
Display resolution0.1°C (0.1°F)
Accuracy±1°C when temp: -20°C to 50°C RH: 40% to 90%
±2°C when temp: -20°C to 50°C RH: 20% to 40%
±4°C when RH: 10% to 20%
Wet bulb temperatureRange-16°C to 50°C, (3°F to 122°F)
Display resolution0.1°C, (0.1°F)
Accuracy±1.2°C when RH: 20% to 90% temp: -20°C to 60°C
±2.1°C when RH: 10% to 20%
Volume flow rate (in a duct)Range0 to 3,965 M3/m, (0 to 140,000 cfm)
Display resolution0.001 M3/min, (1 cfm)
AccuracyN/A: The volume flow calculation will be a simple average of the data points times the duct area
% outside air (based on temperature)Range0 to 100%
Display resolution0.1
% outside air (based on CO2)Range0 to 100%
Display resolution0.1% N/A
General Specifications
Operating and storage temperature-20°C to 50°C (-4°F to 122°F)
Humidity10% to 90% (non-condensing)
AltitudeUp to 2000 m (6562 ft)
Shock and vibrationMIL-PRF-28800F: Class 2
Multi-language interfaceEnglish, French, Spanish, Portuguese and German
BatteryRechargeable Li-Ion (primary), three-AA (backup)
Data logging25,000 records (continuous), 99 records (discrete)
WarrantyTwo-years

Models: Fluke 975 AirMeter™

Fluke 975
Fluke 975 AirMeterTM

  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getContent, 23.81ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: HTTP status code of 404 was returned;
  • y_2025, m_3, d_12, h_9
  • bvseo_bulk, prod_bvrr, vn_bulk_3.0.42
  • cp_1, bvpage1
  • co_hasreviews, tv_0, tr_3
  • loc_en_US, sid_3840950239284, prod, sort_[SortEntry(order=SUBMISSION_TIME, direction=DESCENDING)]
  • clientName_fluke
  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getReviews, 22.57ms
  • REVIEWS, PRODUCT
Please enable cookies to view product reviews.