iFlex가 포함된 393 FC CAT III 1500V True-rms 클램프 미터

  • 393 FC CAT III 1500 V True-rms Clamp Meter
  • The Fluke 393 clamp meter has a very thin jaw for cramped combiner boxes, but still clamps around a 34 mm cable.
  • Fluke 393 FC clamp calculates and dsiplay dc power (kVA) enerated by a solar panel
  • Measurements sent to a smartphone and the cloud via Fluke Connect software.
  • Video Player is loading.
    Current Time 0:00
    Duration 0:00
    Loaded: 0%
    Stream Type LIVE
    Remaining Time 0:00
     
    1x
      • Chapters
      • descriptions off, selected
      • en (Main), selected
    1. 393 FC CAT III 1500 V True-rms Clamp Meter
    2. The Fluke 393 clamp meter has a very thin jaw for cramped combiner boxes, but still clamps around a 34 mm cable.
    3. Fluke 393 FC clamp calculates and dsiplay dc power (kVA) enerated by a solar panel
    4. Measurements sent to a smartphone and the cloud via Fluke Connect software.
    5. Fluke 393 FC CAT III 1500 V True-rms Clamp Meter

    주요 기능

    • CAT III 1500V 정격 클램프 미터를 사용하여 안전하게 측정
    • 혼잡한 컴바이너 박스에서 케이블에 접근할 수 있는 얇은 측정턱
    • 실외용의 견고한 IP54 등급 
    • DC 전력 측정, 오디오 극성 및 시각적 연속성으로 효율적으로 작동

    제품 개요: iFlex가 포함된 393 FC CAT III 1500V True-rms 클램프 미터

    iFlex가 포함된 Fluke 393 FC CAT III 1500V True-rms Clamp Meter는 다음과 같은 고압 DC 환경에서 작업하는 태양광 발전(PV) 설치 기술자 및 유지보수 전문가를 위해 설계되었습니다. 무정전 전원 공급 장치용 PV 어레이, 풍력, 전기 철도, 데이터 센터 배터리 뱅크 본 클램프 미터는 테스트 리드를 사용하는 경우 최대 1500V DC 및 1000V AC, 클램프 측정턱(jaw) 통해 최대 999.9A DC 또는 AC까지 측정합니다. 포함된 iFlex 플렉시블 전류 프로브는 최대 2,500A의 AC 전류 측정값을 확장했습니다. 393 클램프 미터는 턱이 얇아 비좁은 컴바이너 박스의 케이블에 접근할 수 있습니다. 테스트 리드 또한 고전압 작업을 염두에 두고 설계되었으며 정격은 CAT III 1500V DC입니다.


    기타 주요 기능:
    • IP54 등급, 태양열 어레이와 풍력 시스템에서 야외 작업에 이상적 
    • DC 전력 측정, kVA 단위로 눈금 표시
    • 결선을 잘못 연결하는 것을 방지하는 데 도움이 되는 오디오 극성 표시기
    • 시각적 도통 기능은 디스플레이에 밝은 녹색 빛을 제공하여 어둡고 시끄러운 환경에서 작업할 때 이상적
    • Fluke Connect 소프트웨어를 통한 테스트 결과 기록 및 보고
    • 포함된 iFlex 플렉시블 전류 프로브를 통해 좁은 공간에 있는 케이블에 손쉽게 접근할 수 있습니다.  iFlex 프로브는 매우 작은 공간에서도 잘 휘며, 정확한 전류 측정을 제공합니다.
     

    제품 구성:

    • Fluke 393 FC CAT III 1500V TRMS 클램프 미터
    • 테스트 리드, CAT III 1500V 정격, 직각 플러그, 안전 마개 포함
    • iFlex 18인치 플렉시블 전류 프로브
    • TPAK 자석 걸이 스트랩
    • 프리미엄 휴대용 케이스
    • 3년 품질 보증

    제품 사양: iFlex가 포함된 393 FC CAT III 1500V True-rms 클램프 미터

    사양:   
    일반   
    터미널과 접지 사이의 최대 전압  
    AC1,000V  
    DC1500V  
    배터리2AA IEC LR6 알카라인  
    디스플레이백라이트가 포함된 듀얼 디스플레이  
    자동 전원 꺼짐20분  
    전기   
    정확도   
    정확도는 작동 온도가 18°C-28°C이고 상대 습도가 0%-75%인 상태에서 교정한 후 1년 동안으로 지정됩니다. 정확도 사양은 다음 공식을 따릅니다. ±([판독값의%] + [최소 유효 숫자 수])
    온도 계수28°C 이상 또는 18°C 이하 각각에 대해 (0.1 x 정해진 정확도)를 더합니다.
    AC 전류: 측정턱   
    범위999.9A  
    분해능0.1A  
    정확도2% + 5자리(10Hz ~ 100Hz) 
     2.5% + 5자리(100Hz ~ 500Hz) 
    파고율(50/60Hz)2.5 @600.0A  
     3.0(500.0 A에서)  
     1.42(999.9 A에서)  
     2% 추가(C.F.)가 >2  
    AC 전류: 플렉시블 전류 프로브   
    범위999.9A  
     2500A  
    분해능0.1A(≤999.9A)  
     1A(≤2500A)  
    정확도3% 5자리(10Hz~500Hz) 
    파고율(50/60Hz)2.5 @1400 A  
     3.0(1100 A에서)  
     1.42(2500 A에서)  
     2% 추가(C.F.)가 >2  
    위치 감도   
    NEC 기호
    최적과의 거리i2500-10 Flexi2500-18 Flex오류
    A0.5인치(12.7mm)1.4인치(35.6mm)±0.5 %
    B0.8인치(20.3mm)2.0인치(50.8mm)±1.0 %
    C1.4인치(35.6mm)2.5인치(63.5mm)±2.0 %
    측정 불확실성은 중앙의 기본 도체가 최적의 위치에 있고, 외부 전기장 또는 자기장이 없으며, 작동 온도 범위 내에 있다고 가정합니다.
        
    DC 전류   
    범위999.9A  
    분해능0.1A  
    정확도2 % RD ±5자리[1]  
     [1]0을 사용할 때(B) 오프셋을 보상하는 기능.
    AC 전압   
    범위600.0V  
     1,000V  
    분해능0.1V(≤600.0V)  
     1V(≤1000V)  
    정확도1% RD + 5자리(20Hz ~ 500Hz) 
    DC 전압   
    범위600.0V  
     1500V  
    분해능0.1V(≤600.0V)  
     1V(≤1500V)  
    정확도1% RD ±5자리  
    mV DC   
    범위500.0mV  
    분해능0.1mV  
    정확도1% RD ±5자리  
    암페어 주파수: 측정턱   
    범위5.0Hz~500.0Hz  
    분해능0.1Hz  
    정확도0.5% RD ±5자리  
    트리거 레벨5Hz~10Hz, ≥10A  
     10Hz~100Hz, ≥5A  
     100Hz~500Hz, ≥10A  
    전류 주파수: 플렉시블 전류 프로브   
    범위5.0Hz~500.0Hz  
    분해능0.1Hz  
    정확도0.5% RD ±5자리  
    트리거 레벨5Hz~20Hz, ≥25A  
     20Hz~100Hz, ≥20A  
     100Hz~500Hz, ≥25A  
    전압 주파수   
    범위5.0Hz~500.0Hz  
    분해능0.1Hz  
    정확도0.5% RD ±5자리  
    트리거 레벨5Hz ~ 20Hz, 5V 이상  
     20Hz ~ 100Hz, 5V 이상  
     100Hz ~ 500Hz, 10V 이상  
    DC 전원   
    범위600.0kVA(600.0V dc 범위)  
     1,500kVA(1,500V DC 범위)  
    분해능0.1kVA  
     1kVA  
    정확도2% RD + 2.0kVA  
     2% RD + 20kVA  
    저항   
    범위600.0Ω  
     6000Ω  
     60.00kΩ  
    분해능0.1Ω(≤600.0Ω)  
     1Ω(≤6000Ω)  
     0.01kΩ(≤60.00kΩ)  
    정확도1% RD ±5자리  
    정전 용량   
    범위100.0μF  
     1000μF  
    분해능0.1μF(≤100.0μF)  
     1μF(≤1000μF)  
    정확도1% RD ±5자리  
    돌입 트리거 레벨5A  
    기계적   
    크기(LxWxH)281 mm x 84 mm x 49 mm  
    무게(배터리 포함)520g  
    측정집게 입구34mm  
    플렉시블 전류 프로브 지름7.5mm  
    플렉시블 전류 프로브 케이블 길이   
    (전기 도체 방향)1.8m  
    작업 환경   
    작동 온도-10°C~50°C  
    보관 시 온도-40°C~60°C  
    작동 시 습도비응축(<10°C)  
     ≤90% RH(10°C~30°C에서)  
     ≤75% RH(30°C~40°C에서)  
     ≤45% RH(40°C~50°C에서)  
    작동 고도2000m  
    보관 시 고도12,000m  
    IP(Ingress Protection) 등급IEC 60529: IP54 비 작동  
    전자기파 적합성(EMC)   
    국제IEC 61326-1: 휴대용 전자파 환경 IEC 61326-2-2 CISPR 11: Group 1, Class A
     그룹 1: 장비는 자체 내부 기능에 필요한, 전도적으로 커플링된 무선 주파수 에너지를 의도적으로 생성 및/또는 사용합니다.
    Class A: 장비는 가정용 이외의 모든 시설에서 사용하기 적합하며 가정용으로 사용되는 건물에 제공하는 저전압 전원 공급 네트워크에 직접 연결된 장비에도 적합합니다. 전도 및 방사 방해로 인해 다른 환경에서 전자기 호환성을 확보하는데 잠재적 어려움이 있을 수 있습니다.
    주의: 이 장비는 거주 환경에서는 사용할 수 없으며 이러한 환경에서의 주파수 수신에 대한 적절한 보호를 제공하지 않을 수 있습니다.
    대한민국(KCC)Class A 장비(산업용 방송/통신 장비)
     Class A: 장비는 산업용 전자기파 장비에 대한 요구 사항을 충족하며 판매자 또는 사용자는 이를 주의해야 합니다. 본 장비는 기업 환경 용도이며 가정에서는 사용할 수 없습니다.
    미국(FCC)47 CFR 15 subpart B. 이 제품은 15.103항에 따라 면제 장치로 간주합니다.
    안전   
    일반IEC 61010-1: 오염도 2 
    측정IEC 61010-2-032: CAT III 1500V / CAT IV 600V 
     IEC 61010-2-033: CAT III 1500V / CAT IV 600V 
    무선 라디오   
    라디오 주파수 인증FCC ID: T68-FBLE, IC: 6627A-FBLE 
    무선 라디오 주파수 범위2400MHz~2483.5MHz  
    출력 전압<100mW  
    간소화된 EU 적합성 선언서  
    이로써 Fluke는 이 제품에 포함된 무선 장비가 2014/53/EU 지침에 적합함을 선언합니다.
    EU 선언문의 전문은 다음 인터넷 주소에서 확인하실 수 있습니다:  
    www.fluke.com/en-us/declaration-of-conformity   

    모델: iFlex가 포함된 393 FC CAT III 1500V True-rms 클램프 미터

    393 FC
    iFlex가 포함된 393 FC CAT III 1500V True-rms 클램프 미터

    구매하기

    제품 구성:

    • iFlex가 포함된 Fluke 393 FC CAT III 1500V True-rms 클램프 미터
    • 테스트 리드, CAT III 1500V 정격, 직각 플러그, 안전 마개 포함
    • iFlex 18인치 플렉시블 전류 프로브
    • TPAK 자석 걸이 스트랩
    • 프리미엄 휴대용 케이스
    • 3년 품질 보증

    Fluke Connect는 일부 국가에서 사용할 수 없습니다.

    *일부 모델의 경우 일부 국가에서는 구입할 수 없습니다. 해당 지역의 Fluke 담당자에게 확인하십시오.

    ©2025  Fluke Corporation. 모든 상표는 해당 소유자의 재산입니다. 스마트폰, 무선 서비스와 데이터 요금제는 구매 내역에 포함되지 않습니다. 최초 5GB의 저장소는 무료로 제공됩니다. iOS 8 이상을 실행하는 iPhone 4s, (iPad에서 iPhone 프레임 내의) iPad, Android 4.3.x 이상을 실행하는 Samsung Galaxy S4 및 Android™ 4.4.x 이상을 실행하는 Samsung Galaxy S, Nexus 5, HTC One, One M8과 호환됩니다. Apple 및 Apple 로고는 미국 및 그 외의 국가에서 Apple Inc.의 등록 상표입니다. App Store는 Apple Inc.의 서비스 마크입니다. Google Play는 Google Inc.의 상표입니다.