Product Selection Guide: IR windows

Use our product selection guide to find the IR window that fits your needs best.
 
RemoveRemove
 
 
F CV201 02A KO
Discontinued
Fluke CV401 ClirVu® 95 mm (4 in) Infrared Window
 
Fluke CV201 ClirVu® 50 mm (2 in) Infrared WindowFluke CV401 ClirVu® 95 mm (4 in) Infrared Window
 
Size51 mm (2 in)96 mm (4 in) 
Voltage rangeAnyAny 
NEMA environment typeType 4/12 (indoor/outdoor)Type 4/12 (indoor/outdoor) 
AutoGround™   
ClirVu® Optic   
Operating temperature-40 °C to +232 °C (-40 °F to +450 °F)-40 °C to +232 °C (-40 °F to +450 °F) and +260 °C (+500 °F) intermittent 
Arc-tested (IEEE C27.20.7)68 kA for 30 cycles @ 60 Hz at KEMA64 kA for 30 cycles @ 60 Hz at KEMA 
UL 50 V component recognition   
UL 50/NEMA environmental ratingNEMA type 4/17NEMA type 4/13 
UL 1558   
CSA C22.2 No.   
CSA type ratingType 9Type 5 
IP ratingIP 67 at TUVIP 67 at TUV 
Lloyd's RegisterUp to 11 kV marine switchgear, indoor or outdoor (offshore only)Up to 11 kV marine switchgear, indoor or outdoor (offshore only) 
Vibration ratingIEC60068-2-6IEC60068-2-6 at TUV 
Humidity rateIEC60068-2-3IEC60068-2-3 at TUV 
Actual mounting hole diameter required61.37 mm (2.416 in)115.42 mm (4.544 in) 
Greenlee punch kit - punch/die76BB = 441AV / 442AV742BB = 2984AV / 2983AV 
Door latchSecurity keySecurity key 
Install time10 minutes or less6 minutes or less 
Optic insert diameter51 mm (1.97 in)96 mm (3.74 in) 
WarrantyLifetime replacement against manufacturing defectsLifetime replacement against manufacturing defects