Fluke v3003 FC Wireless AC-DC Voltage Measurement Kit
Key Features
The Fluke FC Wireless v3003 AC-DC Voltage Measurement Kit
The Fluke 3000 FC Series Wireless Multimeter with the Fluke Connect® app has all the essentials for convenient test and measurement troubleshooting:
- AC and DC voltage measurements to 1000V
- AC and DC current with 0.01 mA resolution
- Continuity, resistance, diode test, capacitance and frequency measurements
- MIN/MAX recording
- CAT III 1000 V, Cat IV 600 V; IP54
With the Fluke v3000 FC Wireless AC Voltage Module you can:
- Measure up to 1000 V True-RMS AC
- Use as a standalone meter or as part of the system
- Use the logging function for recording and saving up to 65,000 readings
The Fluke v3001 FC Wireless DC Voltage Module lets you:
- Measure up to 1000 V DC
- Use as a standalone meter or as part of the system
- Use the logging function for recording and saving up to 65,000 readings
Product overview: Fluke v3003 FC Wireless AC-DC Voltage Measurement Kit
The FC Wireless v3003 AC-DC Voltage Measurement Kit is part of the Fluke Connect team of wireless test tools
Connect the v3000 FC Wireless AC Voltage and v3001 FC Wireless DC Voltage Modules to your test points, and view the results up to 20 meters away on the 3000 FC Wireless Digital Multimeter.
You'll save time, with less run-around collecting multiple measurements. Use multiple modules for measurements on three-phase systems, as a stand-alone measurement tool or combine with other Fluke Connect® modules as a system for multiple measurements.
From short distances, you can even view readings from modules through closed electrical panels. Plus no more writing down data as the FC Wireless Voltage Modules capture up to 65,000 sets of time stamped min/max/avg readings, using the optional PC adapter. Fluke Connect wireless test tools also offer increased safety by letting you view readings in a separate location from the test point.
Now you can take readings on moving machinery, with only the measurement module in harm's way.
Specifications: Fluke v3003 FC Wireless AC-DC Voltage Measurement Kit
Fluke 3000 FC Wireless Digital Multimeter
* For all specifications: accuracy is specified for one year after calibration, at operating temperatures of 18°C to 28°C, with relative humidity at 0% to 90%. Accuracy specifications take the form of ±([% of Reading ] + [ Number of least significant digits ]).
Detailed Specifications | |||||
AC Voltage | |||||
Range 1 | Resolution | Accuracy 2 3 4 | Accuracy 2 3 4 | ||
45 Hz to 500 Hz | 500 Hz to 1 kHz | ||||
600.0 mV | 0.1 mV | 1.0% + 3 | 2.0% + 3 | ||
6.000 V | 0.001 V | ||||
60.00 V | 0.01 V | ||||
600.0 V | 0.1 V | ||||
1000 V | 1 V | ||||
1. All AC voltage ranges are specified from 1% of range to 100% of range. 2. Crest factor of ≤ 3 at full scale up to 500 V, decreasing linearly to crest factor < 1.5 at 1000 V. 3. For non-sinusoidial waveforms, add ±(2% of reading + 2% full scale) typical, for crest factor up to 3. 4. Do not exceed 107 V-Hz. | |||||
DC Voltage, Continuity, Resistance, Diode Test and Capacitance | |||||
Function | Range | Resolution | Accuracy | ||
mV | 600.0 mV | 0.1 mV | 0.09% + 2 | ||
V | 6.000 V | 0.001 V | 0.09% + 2 | ||
60.00 V | 0.01 V | ||||
600.0 V | 0.1 V | ||||
1000 V | 1 V | 0.15% + 2 | |||
Ω | 600 Ω | 1 Ω | Meter beeps at < 25 Ω, beeper detects opens or shorts of 250 μs or longer. | ||
Ω | 600.0 Ω | 0.1 Ω | 0.5% + 2 | ||
6.000 kΩ | 0.001 kΩ | 0.5% + 1 | |||
60.00 kΩ | 0.01 kΩ | ||||
60.00 kΩ | 0.1 kΩ | ||||
600.0 kΩ | 0.001 MΩ | ||||
50.00 MΩ | 0.01 MΩ | 1.5% + 3 | |||
Diode test | 2.000 V | 0.001 V | 1% + 2 | ||
µF | 1000 nF | 1 nF | 1.2% + 2 | ||
10.00 μF | 0.01 μF | ||||
100.0 μF | 0.1 μF | ||||
9999 μF1 | 1 μF | 10% typical | |||
1. In the 9999 μF range for measurements to 1000 μF, the measurement accuracy is 1.2% + 2. | |||||
AC and DC Current | |||||
Function | Range 1 | Resolution | Accuracy | ||
mA AC (45 Hz to 1 kHz) | 60.00 mA | 0.01 mA | 1.5% + 3 | ||
400.0 mA 3 | 0.1 mA | ||||
mA DC 2 | 60.00 mA | 0.01 mA | 0.5% + 3 | ||
400.0 mA 3 | 0.1 mA | ||||
1. All AC current ranges are specified from 5% of range to 100% of range. 2. Input burden voltage (typical): 400 mA input 2 mV/mA. 3. 400.0 mA accuracy specified up to 600 mA overload. | |||||
Frequency | |||||
Range | Resolution | Accuracy 1 | |||
99.99 Hz | 0.01 Hz | 0.1% + 1 | |||
999.9 Hz | 0.1 Hz | ||||
9.999 kHz | 0.001 kHz | ||||
99.99 kHz | 0.01 kHz | ||||
1. Frequency is specified up to 99.99 kHz in volts and up to 10 kHz in amps. | |||||
Input Characteristics | |||||
Function | Overload protection | Input impedance (nominal) | Common mode rejection ratio (1 kΩ unbalance) | Normal mode rejection | |
1100 Vrms | > 10 MΩ < 100 pF | > 120 dB at DC, 50 Hz or 60 Hz | > 60 dB at 50 Hz or 60 Hz | ||
1100 Vrms | > 10 MΩ < 100 pF | > 60 dB, DC to 60 Hz | |||
1100 Vrms | > 10 MΩ < 100 pF | > 120 dB at DC, 50 Hz or 60 Hz | > 60 dB at 50 Hz or 60 Hz | ||
Open circuit test voltage | Full scale voltage | Typical short circuit current | |||
To 6 MΩ | 50 MΩ | ||||
1100 Vrms | < 2.7 VDC | < 0.7 VDC | < 0.9 VDC | < 350 mA | |
1100 Vrms | < 2.7 VDC | 2.000 VDC | < 1.1 mA | ||
mA Function | |||||
Overload Protection | Fused, 44/100 A, 1000 V FAST Fuse | ||||
Overload | 600 mA overload for 2 minutes maximum, 10 minutes rest minimum | ||||
MIN/MAX Recording Accuracy | |||||
DC functions | The specified accuracy of the measurement function ±12 counts for changes > 350 mS in duration. | ||||
AC functions | The specified accuracy of the measurement function ±40 counts for changes > 900 mS in duration. | ||||
General Specifications | |||||
Maximum voltage between any terminal and earth ground | 1000 VDC or AC rms | ||||
Ω fuse protection from A inputs | 0.44 A (44/100 A, 440 mA), 1000 V FAST Fuse, Fluke specified part only | ||||
Display (LCD) | Update rate | 4/sec | |||
Volts, amps, ohms | 6000 counts | ||||
Frequency | 10,000 counts | ||||
Capacitance | 1,000 counts | ||||
Battery type | Three AA Alkaline batteries, NEDA 15A IEC LR6 | ||||
Battery life | 250 hours minimum | ||||
RF communications | 2.4 GHZ ISM Band | ||||
RF communication range | Open air, unobstructed | Up to 20 m | |||
Obstructed, sheetrock wall | Up to 6.5 m | ||||
Obstructed, concrete wall, or steel electrical enclosure | Up to 3.5 m | ||||
Temperature | Operating | -10°C to 50°C | |||
Storage | -40°C to 60°C | ||||
Temperature coefficient | 0.1 x (specified accuracy) / °C (<18°C or >28°C) | ||||
Relative humidity | 0% to 90% (0°C to 35°C) 0% to 75% (35°C to 40°C) 0% to 45% (40°C to 50°C) | ||||
Altitude | Operating | 2,000 m | |||
Storage | 12,000 m | ||||
Electromagnetic compatibility EMI, RFI, EMC, RF | EN 61326-1:2006, EN 61326-2-2:2006 ETSI EN 300 328 V1.7.1:2006, ETSI EN 300 489 V1.8.1:2008, FCC Part 15 Subpart C Sections 15.207, 15.209, 15.249 FCCID : FCC: T68-FDMMBLE IC: 6627A-FDMMBLE | ||||
Safety compliance | ANSI/ISA 61010-1 / (82.02.01) | 3rd edition | |||
CAN/CSA-C22.2 No 61010-1-12 | 3rd edition | ||||
UL 61010-1 | 3rd edition | ||||
IEC/EN 61010-1 | 2010 | ||||
Certifications | CSA, FCC, CE | ||||
Ingress Protection (IP) rating | IP54 | ||||
Pollution degree | 2 | ||||
Size (H x W x L) | 4.75 x 9.3 x 20.7 cm (1.87 x 3.68 x 8.14 in) | ||||
Weight | 340 g (12 oz) | ||||
Warranty | Three years | ||||
Not compatible with Fluke CNX test tools |
Fluke v3000 FC Wireless AC Voltage Module
Accuracy is specified as ±([% of reading] + [number of least significant digits]). All ranges are autoranging.
Accuracy is specified from 5% to 100% of the range obtained by autoranging, from 18°C to 28°C.
Specifications | ||
Range ¹ / Resolution | 6.000 V / 0.001 V 60.00 V / 0.01 V 600.0 V / 0.1 V 1000 V / 1 V | |
Accuracy 2 3 4 | 45 Hz to 500 Hz | 1.0% + 3 |
500 Hz to 1 kHz | 2.0% + 3 | |
1. All AC voltage ranges are specified from 1% of range to 100% of range. 2. Crest factor of ≤ 3 at full scale up to 500 V, decreasing linearly to crest factor < 1.5 at 1000 V. 3. For non-sinusoidial waveforms, add ±(2% of reading + 2% full scale) typical, for crest factor up to 3. 4. Do not exceed 107 V-Hz. | ||
General Specifications | ||
LCD w/ backlight | 3½ digits, 6000 counts, updates 4/sec | |
Battery type | 2 AA, NEDA 15 A, IEC LR6 | |
Battery life | 400 Hours | |
Memory | Record up to 65000 readings | |
RF communications | 2.4 GHZ ISM Band | |
RF communication range | Open air, unobstructed | Up to 20 m |
Obstructed, sheetrock wall | Up to 6.5 m | |
Obstructed, concrete wall or steel electrical enclosure | Up to 3.5 m | |
Operating temperature | -10°C to +50°C | |
Storage temperature | -40°C to +60°C | |
Temperature coefficient | 0.1 x (specified accuracy) / °C (< 18°C or > 28°C) | |
Operating humidity | 90% at 35°C, 45% at 40°C, 45% at 50°C | |
Altitude | Operating | 2,000 m |
Storage | 12,000 m | |
EMC | EN 61326-1:2006 | |
Safety compliance | ANSI/ISA 61010-1 / (82.02.01) | 3rd edition |
CAN/CSA-C22.2 No 61010-1-12 | 3rd edition | |
UL 61010-1 | 3rd edition | |
IEC/EN 61010-1 | 2010 | |
Safety rating | CAT IV 600 V, CAT III 1000 V | |
Certifications | CSA, CE, FCC: T68-FBLE IC: 6627A-FBLE | |
Ingress Protection (IP) rating | IP42 | |
Pollution Degree | 2 | |
Size (H x W x D) | 16.5 x 6.35 x 1.4 cm (6.5 x 2.5 x 1.4 in) | |
Weight | .22 kg (8 oz) | |
Warranty | Three years | |
Not compatible with Fluke CNX test tools |
Fluke v3001 FC Wireless DC Voltage Module
Accuracy is specified for 1 year after calibration, at operating temperatures of 18°C to 28°C, with relative humidity at 0% to 90%. Accuracy specifications take the form of ±([% of Reading ] + [Number of least significant digits]).All ranges are autoranging. Accuracy is specified from the range obtained by autoranging, from 18°C to 28°C.
Voltage Specifications | ||
Function | ||
mVDC | Range ¹ / Resolution | 600.0 mV / 0.1 mV |
Accuracy | 0.09% + 3 | |
VDC | Range ¹ / Resolution | 6.000 V / 0.001 V 60.00 V / 0.01 V 600.0 V / 0.1 V |
Accuracy | 0.09% + 3 | |
Range ¹ / Resolution | 1000 V / 1 V | |
Accuracy | 0.15% + 2 | |
General Specifications | ||
LCD w/ backlight | 3 ½ digits, 6000 counts, 4/sec update rate | |
Battery type | 2 AA Alkaline batteries, NEDA 15A, IEC LR6 | |
Log rate/interval | Adjustable by PC from 1 sec to 1 hr, default 1 min | |
Battery life | 400 hours minimum | |
Memory | Record up to 65,000 readings | |
RF communications | 2.4 GHz ISM Band | |
RF communication range | Open air, unobstructed | Up to 20 m |
Obstructed, sheetrock wall | Up to 6.5 m | |
Obstructed, concrete wall or steel electrical enclosure | Up to 3.5 m | |
Operating temperature | -10°C to +50°C | |
Storage temperature | -40°C to +60°C | |
Temperature coefficient | 0.1 x (specified accuracy) / °C (< 18°C or > 28°C) | |
Relative humidity | 0% to 90% (0°C to 35°C), 0% to 75% (35°C to 40°C), 0% to 45% (40°C to 50°C) | |
EMC | IEC 61236-1, Portable | |
Safety compliance | IEC 61010-1, 600 V CAT IV / 1000 V CAT III, 3rd edition, Pollution Degree 2 | |
Certifications | CSA, CE, FCC: T68-FBLE IC: 6627A-FBLE | |
Ingress Protection (IP) rating | IP42 | |
Size (H x W x D) | 160 x 66 x 38 mm (6.3 x 2.6 x 1.5 in) | |
Weight | 0.255 kg (9 oz) | |
Warranty | Three years | |
Not compatible with Fluke CNX test tools |
Models: Fluke v3003 FC Wireless AC-DC Voltage Measurement Kit
Includes:
- Fluke 3000 FC Series Wireless Multimeter
- Fluke v3000 AC Voltage Module
- Fluke v3001 DC Voltage Module
- TL175 Test Leads
- TL224 Test Leads
- TL222 Test Leads
- AC175 Alligator Clips
- AC285 Alligator Clips
- AC220 Alligator Clips
- Magnetic hanging straps
Manuals + Resources: Fluke v3003 FC Wireless AC-DC Voltage Measurement Kit
- 3000 FC | Users manual
- 3000 FC | Quick reference guide
- 3000 FC | Safety sheet
- a3000 FC | Quick reference guide
- a3000 FC | Safety sheet
- a3001 FC | Quick reference guide
- a3001 FC | Safety sheet
- a3001 FC | Safety sheet supplement
- a3002 FC | Quick reference guide
- a3002 FC | Calibration manual
- a3002 FC | Safety sheet
- Fluke Connect | Quick reference guide
- Fluke Connect Wi-Fi to Thermal Imager | Quick reference guide
- ir3000 FC | Quick reference guide
- pc 3000 FC | Instruction sheet
- Radio Frequency Data Class B | Instruction sheet
- t3000 FC | Quick reference guide
- t3000 FC | Safety sheet
- t3000 FC | Safety sheet supplement
- v3000 FC v3001 FC | Quick reference guide
- v3000 FC v3001 FC | Safety sheet
- v3001 FC | Calibration manual
- Saving measurements with AutoRecord™ measurements
- How to email a measurement using the Fluke Connect app
- What is Fluke Connect®
- Connecting multiple tools at the same time with Fluke Connect®
- Performing predictive maintenance with Fluke Connect™
- Connecting the T3000 FC with the Fluke Connect™ app
- How to create an equipment baseline with EquipmentLog™ history
- Measuring from a safe distance using the Fluke Connect™ app
- Identifying intermittent conditions with TrendIt™ graphs
- Introduction to 789FC
- How to save measurements to EquipmentLog™ history
- Share equipment health with EquipmentLog™ history
- How to share measurements on equipment using the Fluke Connect™ app
- Using ShareLive™ video call to share live measurements and video
- How to record measurements and graphs
- Viewing and graphing three phase measurements
- Measurement history in one place using EquipmentLog™ history
- Connecting a thermal imager to your iPhone