The Fluke 87V Industrial Multimeter provides the resolution and accuracy to efficiently troubleshoot motor drives, plant automation, power distribution, and electromechanical equipment even in loud, high-energy, and high-altitude locations. PRV240 is a portable pocket sized battery powered voltage source to verify proper voltage measurement.
Specifications: Fluke 87V Digital Multimeter with PRV240 Proving Unit Kit
Fluke 87V Digital Multimeter | ||
Voltage DC | Maximum voltage | 1000 V |
Accuracy | ±(0.05% + 1) | |
Maximum resolution | 10 µV | |
Voltage AC | Maximum voltage | 1000 V |
Accuracy | ±(0.7% + 2) True RMS | |
AC bandwidth | 20 kHz with low pass filter; 3 dB @ 1 kHz | |
Maximum resolution | 0.1 mV | |
Current DC | Maximum amps | 10 A (20 A for 30 seconds maximum) |
Amps accuracy | ±(0.2% + 2) | |
Maximum resolution | 0.01 µA | |
Current AC | Maximum amps | 10 A (20 A for 30 seconds maximum) |
Amps accuracy | ±(1.0% + 2) True RMS | |
Maximum resolution | 0.1 µA | |
Resistance | Maximum resistance | 50 MΩ |
Accuracy | ±(0.2% + 1) | |
Maximum resolution | 0.1 Ω | |
Capacitance | Maximum capacitance | 9,999 µF |
accuracy | ±(1% + 2) | |
Maximum resolution | 0.01 nF | |
Frequency | Maximum frequency | 200 kHz |
Accuracy | ±(0.005% + 1) | |
Maximum resolution | 0.01 Hz | |
Duty cycle | Maximum duty cycle | 99.9% |
Accuracy | ±(0.2% per kHz + 0.1%) | |
Maximum resolution | 0.1% | |
Temperature measurement | –200.0 °C – 1090 °C –328.0 °F – 1994.0 °F excluding probe | |
80 BK temperature probe | –40.0 °C – 260 °C –40.0 °F – 500 °F, 2.2 °C or 2% whichever is greater | |
Conductance | Maximum conductance | 60.00 nS |
Accuracy | ±(1.0% + 10) | |
Maximum resolution | 0.01 nS | |
Diode | Range | 3 V |
Resolution | 1 mV | |
Accuracy | ±(2% + 1) | |
Duty cycle range | Accuracy | Within ±(0.2% per kHz + 0.1%) |
Environmental Specifications | ||
Operating temperature | –20 °C to + 55 °C | |
Storage temperature | –40 °C to + 60 °C | |
Humidity (without condensation) | 0% – 90% (0 °C – 35 °C) 0% – 70% (35 °C – 55 °C) | |
Operating Altitude | 2000 m | |
Safety Specifications | ||
Overvoltage category | EN 61010–1 to 1000 V CAT III, 600V CAT IV | |
Agency approvals | CE, CSA, RCM | |
Mechanical and General Specifications | ||
Size | 201 x 98 x 52 mm (with holster) | |
Weight | 355 g 624 g – with holster | |
Display | Digital | 6000 counts updates 4/sec. 19,999 counts in high–resolution mode |
Analog | 32 segments, updates 40/sec | |
Frequency | 19,999 counts, updates 3/sec at > 10 Hz | |
Warranty | Lifetime | |
Battery Life | Alkaline | ~400 hours typical, without backlight |
Shock | 1 Meter drop per IEC 61010–1:2001 | |
Vibration | Per MIL–PRF–28800 for a Class 2 instrument |