Practical Bonding Tests with a Digital Multimeter

Testing electrical bonds is essential for ensuring the safety and reliability of electrical systems. While specialized earth-ground meters are ideal for comprehensive testing, digital multimeters (DMMs) can still be effectively used for certain practical bonding tests.

Fluke 87-V Digital Multimeter Kit with Probes

One practical application for a DMM is checking if the ground pin in a duplex receptacle is incorrectly bonded to the neutral. Here’s a step-by-step guide on how to perform this test using a digital multimeter.

Why Check Bonding in a Duplex Receptacle?

In electrical systems, the ground and neutral leads should only be bonded at one point - the main service panel. An improper bond at any other point can create safety hazards and interfere with the electrical system's operation.

By performing this test, you can ensure that the ground and neutral are correctly bonded only where they should be.

Tools Needed

  • Digital multimeter
  • High-wattage load (e.g., a hairdryer)

Step-by-Step Procedure

  1. Prepare Your Workspace
    • Make sure that nothing is plugged into either outlet to start.
  2. Initial Voltage Measurement
    • Insert the multimeter probes into the receptacle: one probe into the neutral slot (the wider slot on the left-hand side) and the other into the ground slot (the D-shaped socket).
    • Set your multimeter to measure AC voltage.
    • Measure the voltage. The multimeter should read 0.0 volts or a few millivolts. This establishes the baseline voltage with no load.
  3. Apply Load and Measure Again
    • Plug the hairdryer into the other socket of the same duplex receptacle.
    • Turn the hairdryer on to its highest setting, typically placing a one-kilowatt load on the circuit.
    • Measure the voltage again between the neutral and ground with the hairdryer running.
  4. Interpret the Results
    • Proper bonding: If the ground and neutral are bonded correctly only at the service panel, you should see an increase in the millivolt reading due to the voltage drop caused by the current flowing in the neutral wire.
    • Improper bonding: If there is no change in the voltage reading, it suggests that the ground and neutral may be incorrectly bonded within the receptacle box or somewhere nearby on the same circuit.

Why This Test Works

This test relies on the principle that under normal operation, the ground should not carry current. The neutral, on the other hand, does carry current. When a high-wattage load is applied, a voltage drop occurs along the neutral wire, which should be reflected in the voltage measurement between neutral and ground if they are properly bonded at the service panel.

If the neutral and ground are improperly bonded at the receptacle or nearby in the circuit, there will be no significant voltage difference because the current will flow through both the neutral and ground paths, negating the voltage drop.

Tips for Accurate Testing

  • Ensure good contact: Make sure the multimeter probes are making good contact with the receptacle slots.
  • Safety first: Ensure that you’re wearing the correct PPE such as safety glasses and gloves.
  • Repeat measurements: For consistency, you may want to repeat the measurements a few times to ensure accuracy.

Conclusion

While a digital multimeter is not a substitute for a specialized earth-ground meter, it can be a useful tool for practical bonding tests in less critical applications. By following the procedure detailed in this article, you can determine if there is an improper bond between neutral and ground in a duplex receptacle.

This simple test can help you identify potential issues and ensure the safety and proper operation of your electrical system. Always remember to exercise caution and follow safety protocols when working with electrical systems.