      1. Fluke 1662 Multifunction Installation Tester
      2. Fluke takes product testing seriously

      Key features

      Read more

      Product overview: Fluke 1662 Multifunction Testers

      Fluke 1662 Multifunction Installation Tester delivers solid, basic installation testing features

      The Fluke 1662 installation tester gives you Fluke reliability and all the basic testing power you need for day-in, day-out installation testing. It tests to all local regulations and is easy and intuitive to use. Additional helpful features like the On/Off switchable auto-start for RCD and loop test, and self-test save time and give you more confidence in your results.

      • Measures RCD switching time and tripping level (ramp test)
      • Measures trip time and current for RCD type A & AC in one test
      • Measures RCD variable current
      • Provides automatic RCD test sequence
      • Includes Z-max memory for loop tests to support easy evaluation of the highest loop test value
      • Provides unique zero adapter for fast, reliable and accurate test lead and mains cord compensation
      • Includes a phase sequence indicator
      • Comes with hard carrying case, padded carrying and waist strap, and remote control probe and lead

      Specifications: Fluke 1662 Multifunction Testers

      AC voltage measurement
      Range500 V
      Resolution0.1 V
      Accuracy 45 Hz – 66 Hz0.8% + 3
      Input impedance360 kΩ
      Overload protection660 V rms
      Continuity testing (RLO)
      Range (autoranging)20 Ω / 200 Ω / 2000 Ω
      Resolution0.01 Ω / 0.1 Ω / 1 Ω
      Open Circuit Voltage>4 V
      Insulation resistance measurement (RISO)
      Accuracy of test voltage (at rated test current)+10%, -0%
      Test voltage100 V
      250 V
      500 V
      1000 V
      Insulation resistance range20 MΩ / 50 MΩ
      20 MΩ / 100 MΩ
      20 MΩ / 200 MΩ
      20 MΩ / 200 MΩ / 500 MΩ
      20 MΩ / 200 MΩ / 1000 MΩ
      Resolution0.01 MΩ / 0.1 MΩ
      0.01 MΩ / 0.1 MΩ
      0.01 MΩ / 0.1 MΩ
      0.01 MΩ / 0.1 MΩ / 1 MΩ
      0.01 MΩ / 0.1 MΩ / 1 MΩ
      Test current1 mA @ 50 kΩ
      1 mA @ 100 kΩ
      1 mA @ 250 kΩ
      1 mA @ 500 kΩ
      1 mA @ 1 MΩ
      Loop and line impedance (ZI)
      Range10 Ω / 0.001 Ω / High current mΩ mode
      Resolution0.01 Ω / 0.1 Ω / 1 Ω
      Prospective earth fault current, PSC test
      Range1000 A / 10 kA (50 kA)
      Resolution1 A / 0.1 kA
      ComputationProspective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
      RCD testing, RCD types tested
      RCD TypeA4, AC¹, G², S³
      Notes¹Responds to AC
      ²General, no delay
      ³Time delay
      4Responds to pulsed signal
      5Responds to smooth DC signal
      Tripping speed test (ΔT)
      Current settings¹10-30-100-300-500-1000 mA – VAR
      10-30-100 mA
      Multiplierx ½, x 1
      x 5
      Measurement rangeRCD Type G310 ms
      50 ms
      RCD Type S510 ms
      160 ms
      Notes¹1000 mA type AC only
      700 mA maximum type A in VAR mode
      VAR mode not available for type B.
      RCD/FI-Tripping Current Measurement/Ramp Test (IΔN)
      Current range30% to 110% of RCD rated current¹
      Step size10% of IΔN²
      Dwell timeType G300 ms/step
      Type S500 ms/step
      Measurement accuracy±5%
      Specified trip current ranges (EN 61008-1)50% to 100% for Type AC
      35% to 140% for Type A (>10 mA)
      35% to 200% for Type A (≤10 mA)
      50% to 200% for Type B
      ²5% for Type B
      Notes¹30% to 150% for Type A IΔN > 10 mA
      30% to 210% for Type A IΔN = 10 mA
      20% to 210% for Type B
      Phase Sequence Indication
      Iconicon phase sequence indicator

       Phase Sequence indicator is active.

      General Specifications
      Size (L x W x H)10 x 25 x 12.5 cm
      Weight (incl. batteries)1.3 (kg)
      Battery size, quantityType AA, 6 ea.
      SealingIP-40
      SafetyComplies with EN/IEC 61010-1 and  EN/IEC 61010-2-034
      OvervoltageCAT III / 500V; CAT IV 300V
      PerformanceEN61557-1 to EN61557-7 and EN61557-10

      Models: Fluke 1662 Multifunction Testers

      FLK-1662
      Fluke 1662 Multifunction Installation Tester

      Buy it
      Includes:
      • 6x AA (IEC LR6) cell batteries
      • C1600 hard carrying case
      • Zero adapter
      • Heavy duty mains cord
      • STD standard test lead set
      • Padded carrying and waist strap
      • Quick reference guide
      • TP165X remote control probe and lead
      • y_2025, m_3, d_13, h_9CST
      • bvseo_bulk, prod_bvqa, vn_bulk_3.0.42
      • cp_1, bvpage1
      • co_hasquestionsanswers, tq_1
      • loc_en_US, sid_3840949354548, prod, sort_[SortEntry(order=LAST_APPROVED_ANSWER_SUBMISSION_TIME, direction=DESCENDING)]
      • clientName_fluke
      • bvseo_sdk, p_sdk, 3.2.1
      • CLOUD, getContent, 50.19ms
      • QUESTIONS, PRODUCT
      • bvseo_sdk, p_sdk, 3.2.1
      • CLOUD, getReviews, 21.57ms
      • REVIEWS, PRODUCT
      • bvseo-msg: HTTP status code of 404 was returned;
      Please enable cookies to view product reviews.